NEC Electrical Wire Size Chart & Voltage Drop Calculator
Calculate exact NEC copper (Romex NM-B / THHN) and aluminum (SER / MHF) wire gauge sizes from 15A to 200A with live 3% voltage drop upsizing for EV chargers, RV pedestals, and detached shop subpanels.
Wire Gauge & Voltage Drop Sizer
NEC 310.16Engineering Note: Per NEC 210.19 Informational Note, branch circuit voltage drop should stay at or below 3.0% (5.0% combined feeder + branch). Continuous loads (such as EV chargers running ≥ 3 hours) must be sized at 125% of draw (e.g., a 48A EV charger requires a 60A breaker and 6 AWG Copper THHN or 4 AWG Copper NM-B).
6 AWG Copper NM-B or THHN (or 8 AWG THHN in 75°C conduit); ideal for 50A RV & ovens.
6 AWG Copper THHN in conduit (75°C = 65A); Romex NM-B requires 4 AWG (60°C rule).
2 AWG Aluminum MHF/SER (90A–100A residential) or 1 AWG Al / 3 AWG Cu for full 100A.
Per NEC Table 310.12 (83% residential dwelling feeder/service sizing rule).
| Wire Gauge (AWG) | Copper NM-B (60°C) | Copper THHN (75°C) | Aluminum SER/MHF (75°C) | Common Residential / Shop Circuit |
|---|---|---|---|---|
| 14 AWG | 15 Amps | 15 Amps* | Not Allowed | 15A general lighting & bedroom receptacles |
| 12 AWG | 20 Amps | 20 Amps* | Not Recommended | 20A kitchen, bath, garage & outdoor GFCI outlets |
| 10 AWG | 30 Amps | 30 Amps* | 25 Amps | 30A electric dryer, water heater, 30A RV outlet |
| 8 AWG | 40 Amps | 50 Amps | 40 Amps | 40A–50A electric range, hot tub, 32A EV charger |
| 6 AWG | 55 Amps | 65 Amps | 50 Amps | 50A RV/welder, 60A EV charger (THHN conduit only) |
| 4 AWG | 70 Amps | 85 Amps | 65 Amps | 60A–70A subpanel, 60A EV charger (Romex NM-B) |
| 3 AWG | 85 Amps | 100 Amps | 75 Amps | 100A copper detached garage / shop subpanel |
| 2 AWG | 95 Amps | 115 Amps | 90 Amps | 90A aluminum MHF shop subpanel (most cost-effective) |
| 1 AWG | 110 Amps | 130 Amps | 100 Amps | 100A full-rated aluminum subpanel feeder |
| 1/0 AWG | 125 Amps | 150 Amps | 120 Amps | 125A copper/aluminum heavy workshop feeder |
| 2/0 AWG | 145 Amps | 175 Amps | 135 Amps | 200A residential dwelling main service (Copper, NEC 310.12) |
| 4/0 AWG | 195 Amps | 230 Amps | 180 Amps | 200A residential dwelling main service (Aluminum, NEC 310.12) |
*Per NEC 240.4(D), overcurrent protection for 14 AWG, 12 AWG, and 10 AWG copper is strictly capped at 15A, 20A, and 30A respectively. Always verify local AHJ electrical code.
Frequently Asked Questions — Wire Size Chart
What size wire do I need for a 50 amp breaker?
For a 50A circuit (such as a 50A RV hookup, welder, or kitchen range), use 6 AWG Copper NM-B (Romex), 6 AWG Copper THHN (8 AWG THHN is rated 50A at 75°C, though 6 AWG is widely preferred for long runs), or 6 AWG Aluminum SER/MHF (50A at 75°C).
Can I use 6 AWG Romex (NM-B) for a 60 amp EV charger?
No—this is one of the most common electrical inspection failures! Under NEC 334.80, NM-B (Romex) must be sized from the 60°C column, where 6 AWG Copper is rated for only 55 Amps. For a 60A breaker (48A continuous EV charger), you must run 6 AWG Copper THHN in conduit (65A @ 75°C) OR upsize to 4 AWG Copper NM-B.
What size aluminum wire do I need for a 100 amp subpanel in a detached garage or barndominium?
For a full 100A breaker feeding a detached shop or garage subpanel, NEC Table 310.16 requires 1 AWG Aluminum (or 3 AWG Copper) at 75°C. Many builders instead install a 90A breaker using widely available, lower-cost 2-2-2-4 Aluminum Mobile Home Feeder (MHF) cable.