NEC Electrical Wire Size Chart & Voltage Drop Calculator

Calculate exact NEC copper (Romex NM-B / THHN) and aluminum (SER / MHF) wire gauge sizes from 15A to 200A with live 3% voltage drop upsizing for EV chargers, RV pedestals, and detached shop subpanels.

Wire Gauge & Voltage Drop Sizer

NEC 310.16
Common Home & Shop Presets
75 ft
Recommended Minimum NEC Wire SizeCopper • 240V • 50A
8 AWG (Copper THHN)
Voltage Drop
2.43%
−5.8V (234.2V at load)
Min Conduit Size
3/4" PVC/EMT
Typical 3-wire + ground
NEC 3% Rule
PASS
Base ampacity sufficient

Engineering Note: Per NEC 210.19 Informational Note, branch circuit voltage drop should stay at or below 3.0% (5.0% combined feeder + branch). Continuous loads (such as EV chargers running ≥ 3 hours) must be sized at 125% of draw (e.g., a 48A EV charger requires a 60A breaker and 6 AWG Copper THHN or 4 AWG Copper NM-B).

2026 Key Statistics & Quick-Cite Summary: Wire Size Chart
2024 IRC / NEC Verified Reference
50 Amp Wire Size
6 AWG Cu / 4 AWG Al

6 AWG Copper NM-B or THHN (or 8 AWG THHN in 75°C conduit); ideal for 50A RV & ovens.

60 Amp EV Charger
6 AWG Cu THHN

6 AWG Copper THHN in conduit (75°C = 65A); Romex NM-B requires 4 AWG (60°C rule).

100 Amp Subpanel
2 AWG Al / 3 AWG Cu

2 AWG Aluminum MHF/SER (90A–100A residential) or 1 AWG Al / 3 AWG Cu for full 100A.

200 Amp Main Service
4/0 Al / 2/0 Cu

Per NEC Table 310.12 (83% residential dwelling feeder/service sizing rule).

NEC Table 310.16 Residential Copper & Aluminum Wire Size, Breaker & Ampacity Chart
NEC copper NM-B (60C), copper THHN (75C), aluminum SER/MHF (75C) ampacities, conduit sizes, and common home/shop circuits.
Wire Gauge (AWG)Copper NM-B (60°C)Copper THHN (75°C)Aluminum SER/MHF (75°C)Common Residential / Shop Circuit
14 AWG15 Amps15 Amps*Not Allowed15A general lighting & bedroom receptacles
12 AWG20 Amps20 Amps*Not Recommended20A kitchen, bath, garage & outdoor GFCI outlets
10 AWG30 Amps30 Amps*25 Amps30A electric dryer, water heater, 30A RV outlet
8 AWG40 Amps50 Amps40 Amps40A–50A electric range, hot tub, 32A EV charger
6 AWG55 Amps65 Amps50 Amps50A RV/welder, 60A EV charger (THHN conduit only)
4 AWG70 Amps85 Amps65 Amps60A–70A subpanel, 60A EV charger (Romex NM-B)
3 AWG85 Amps100 Amps75 Amps100A copper detached garage / shop subpanel
2 AWG95 Amps115 Amps90 Amps90A aluminum MHF shop subpanel (most cost-effective)
1 AWG110 Amps130 Amps100 Amps100A full-rated aluminum subpanel feeder
1/0 AWG125 Amps150 Amps120 Amps125A copper/aluminum heavy workshop feeder
2/0 AWG145 Amps175 Amps135 Amps200A residential dwelling main service (Copper, NEC 310.12)
4/0 AWG195 Amps230 Amps180 Amps200A residential dwelling main service (Aluminum, NEC 310.12)

*Per NEC 240.4(D), overcurrent protection for 14 AWG, 12 AWG, and 10 AWG copper is strictly capped at 15A, 20A, and 30A respectively. Always verify local AHJ electrical code.

Frequently Asked Questions — Wire Size Chart

What size wire do I need for a 50 amp breaker?

For a 50A circuit (such as a 50A RV hookup, welder, or kitchen range), use 6 AWG Copper NM-B (Romex), 6 AWG Copper THHN (8 AWG THHN is rated 50A at 75°C, though 6 AWG is widely preferred for long runs), or 6 AWG Aluminum SER/MHF (50A at 75°C).

Can I use 6 AWG Romex (NM-B) for a 60 amp EV charger?

No—this is one of the most common electrical inspection failures! Under NEC 334.80, NM-B (Romex) must be sized from the 60°C column, where 6 AWG Copper is rated for only 55 Amps. For a 60A breaker (48A continuous EV charger), you must run 6 AWG Copper THHN in conduit (65A @ 75°C) OR upsize to 4 AWG Copper NM-B.

What size aluminum wire do I need for a 100 amp subpanel in a detached garage or barndominium?

For a full 100A breaker feeding a detached shop or garage subpanel, NEC Table 310.16 requires 1 AWG Aluminum (or 3 AWG Copper) at 75°C. Many builders instead install a 90A breaker using widely available, lower-cost 2-2-2-4 Aluminum Mobile Home Feeder (MHF) cable.